B210LPBP System Sensor Bulk Pack B210LPBP System Sensor, to meet local code and application requirements, System Sensor offers relay, isolator, and sounder base options for 200 Series detectors. Relay bases provide one form C contact relay for control of auxiliary functions, such as door closure and elevator recall.
Isolator bases allow loops to continue to operate under fault conditions and automatically restore when the fault is removed. Sounder bases are available in a combination of temporal 3 and continuous tone model (B200SR) or an addressable model (B200S) that can be activated by the fire alarm control panel based on the event.
200 Series Bases provide a variety of mounting options to meet your installation challenges. Bases come in flanged or flangeless versions for mounting to a variety of junction boxes. See the 200 Series Junction Box Selection Guide on the next page for junction box options. Surface mounting boxes are also available.
The B210LP 6” Mounting Base and the B501 4” Mounting Base are plug in detector bases for IDP style detectors intended for use with Silent Knight IFP-series fire alarm control panels (FACPs). The B210LP and B501 have screw terminals for power (+) and (-) and remote annunciator connections. Communication takes place over the power (+) and (-) lines.
> Features:
• Plug-in mounting provides ease of installation • Tamper-proof feature prevents removal of the detector without the use of a tool • Range of mounting options to meet any application • Rotary address switches for fast installation • Optional remote LED annunciator (PN RA100Z) • SEMS screws • 12–22 AWG wire ranges for installation flexibility • ULListed